This 30kW rack-mounted liquid load bank is our latest R&D product, specially designed for data center applications. It features a high adjustment precision of 0.1kW and integrates key components including a PLC, pressure sensor, flow meter, and temperature sensor. The system uses DN25 stainless steel water pipes and supports a maximum flow rate of 40LPM, making it suitable for testing a variety of data center equipment such as CDUs (Coolant Distribution Units), PDUs (Power Distribution Units), and more.
Working Cycle: Continuous operation.
Ambient temperature: -10℃~40℃
Operating environment humidity: 0~95%
Dimensions: Height 6U, W483 * H264 * D800mm
Instrumentation: Digital metering (V, A, kW) and data logging.
Control Power: Via external 220V AC / Testing circuit.
Inlet water temperature: 5-40℃
Load Elements: High-capacity Nichrome load elements. Elements are fully supported with stainless steel rods and high-temperature refractory ceramics for quick heat discharge.
Safety Features: Over-temperature, over/under voltage, cooling-air loss, and current imbalance protection.
Load Connections: 5-pin IEC plug
Daisy Chained: Multiple load banks can be hooked together for higher load capacity.
Enclosure: Heavy gauge steel outdoor enclosure with powder coat finish. Hinged access doors with lockable latches. Forklift pockets for easy mobility.
SEND INQUIRY
Please fill in fully your information to send email