| Capacity | ||||||
| VA/W | 1KVA/0.9KW | 2KVA/1.8KW | 3KVA/2.7KW | |||
| Input | ||||||
| Voltage Range | Full Load:160±50%VAC~300±50%VAC;Half Load:110±50%VAC~300±50%VAC | |||||
| Frequency Range | 40-70Hz | |||||
| Phase | Single phase two wire+ground wire | |||||
| Distortion | <5% | |||||
| Power factor | 0.99 | |||||
| Generator input | support | |||||
| Output | ||||||
| Voltage | 220 (1±1%)VAC | |||||
| Frequency (same frequency mode) | 47~53Hz/57~63Hz | |||||
| Power Factor | 0.9 | |||||
| Frequency (battery mode) | 50±0.25Hz or 60±0.25Hz | |||||
| Crest ratio | 03:01 | |||||
| Harmonic distortion | ≤3%THD (Linear load) | |||||
| ≤6%THD (Nonlinear load) | ||||||
| Output waveform | Pure Sine Wave | |||||
| Socket | Universal socket *2 | Universal socket *4 | Universal socket *3+Terminal block | |||
| Over Load | 100%-110%: warning sound; 110%-130%:Automatically turns off after 1 minute, or switch to bypass mode when input correct; >130%:Turn off immediately, or switch to bypass mode when the input correct | |||||
| Efficiency | ||||||
| Charging Mode | 85% | 88% | ||||
| Battery Mode | 83% | 85% | ||||
| Battery | ||||||
| Battery Type | 12V/7AH | / | 12V/7AH | / | 12V/7AH | / |
| Battery Number | 3 | 6 | 8 | |||
| Equipment time (full load) | >5mins | >5mins | >5mins | |||
| Charging Time(90%) | 8h | 8h | 8h | |||
| Charge battery (max) | 1.0A | 4.0 | 1.0A | 4.0 | 1.0A | 4.0 |
| Rated charging voltage | 41.0±1%VDC | 82.1±1%VDC | 109.4±1%VDC | |||
| Temperature detection | support | |||||
| Conversion time | ||||||
| Utility to Battery | 0ms | |||||
| Inverter to bypass | 4ms | |||||
| Utility Priority Mode | support | |||||
| Warning Alarm | ||||||
| Battery Mode | alarm every 4 seconds | |||||
| Low Power | alarm every one second | |||||
| Over Load | alarm 2 every second | |||||
| Fault | continuous alarm | |||||
| Shape | ||||||
| Dimension (D*W*H) mm | 350*145*220 | 425*190*320 | ||||
| Net weight(Kg) | 12 | 7 | 24 | 11 | 29 | 12 |
| Connector | ||||||
| Micro RS-232 | Windows,Linux,Sun Solaris,IBM Aix,Compaq True64,SGIRIX,FreeBSD,HP-UX and MAC | |||||
| USB(Optional) | Windows & MAC | |||||
| Rabbet(Optional) | SNMP/AS400 Relay Card/Rs485 | |||||
| EPO(Optional) | Support emergency shutdown |